1. Product Description
Fire Dampers are generally used for control in air distribution system. In the event of fire, Fire Damper will shut automatically, discontinuing airflow into the room, thus, prevent spreading of fire.
This range of Marine Fire Dampers are designed according to special requirements of the Marine Industry, for use in the emergency generator system, air distribution and fire control, engine room ventilation and other related applications. The most significant characteristics of our Marine Type Fire Damper is that it comes with an electrical actuator, which enables rapid closing of the damper blade when an electric signal is sent. Once the damper blade is shut, the control system will send a message to inform the control tower. The Marine Fire Damper can be operated in three ways, the manual operation mode, the electrical operation mode and activation by thermal fuse unit.
|
Our Marine Type Fire Damper has attained DNV Quality System Certificate of Assessment.

|
2. Specification
RECTANGULAR TYPE
| Damper Size |
: |
150<W<1000 (mm), 150<L<1000 (mm) |
| Depth |
: |
D = 200 mm (Standard) |
| Casing |
: |
5.0mm thick mild steel sheet |
| Blade |
: |
3.2mm thick EG sheet |
| Blade Shaft |
: |
SUS304, 2B |
| Fire Rating |
: |
Class A-60 deck, IMO FTP Code Standard |
| Fusible Link |
: |
72 °C |
| Electrical Actuator |
: |
ADS-B101 |
| Finish |
: |
Etching Primer Green |
 |
ROUND TYPE
| Damper Size |
: |
MIN=150mm Ø, MAX=700mm Ø |
| Depth |
: |
D = 200 mm (Standard) |
| Casing |
: |
5.0mm thick mild steel sheet |
| Blade |
: |
3.2mm thick EG sheet |
| Blade Shaft |
: |
SUS304, 2B |
| Fire Rating |
: |
Class A-60 deck, IMO FTP Code Standard |
| Fusible Link |
: |
72 °C |
| Electrical Actuator |
: |
ADS-B101 |
| Finish |
: |
Etching Primer Green |
 |
|
3. CONTROLLER OF MARINE FIRE DAMPER
GENERAL
| Rated Voltage |
: |
DC 24V |
| Operating Voltage |
: |
DC 18V - 30V |
| Rated current |
: |
DC 24V |
| Confirmation |
: |
Operation confirmation signal from built-in microswitch |
| Contact Rating |
: |
DC 30V/2.0A |
| Fusible Link |
: |
72 °C |
| Reset |
: |
Manual Reset |
 |
OPERATION METHOD
The damper is fitted with an electrical actuator which enables rapid closing of the damper blades. It can be operated in three ways.
[1] MANUAL OPERATION MODE
[ Closing ]
Pull the MANUAL LEVER. This actuates thespring to release(ADS-B101) causing the damper blades to close momentarily.
Closed
[ Reset ]
Turn the MANUAL HANDLE counterclockwise until the indicator reaches position "O" on the scale, locking the damper blades.
Reset
[2] ELECTRICAL OPERATION MODE
The electrical actuator closes the damper blades rapidly once signal (D/DC 24V) is received from control centre. Once the damper is closed, confirmation signal and reporting signal will be sent out immediately at any time.
[3] ACTIVATION BY THERMAL FUSE UNIT
A temperature above 72 °C in the damper duct causes the temperature fuse to be melt. The shaft of the fusible link, in turn, unlock the fuse arm to activate the spring in the ADS-B101, thus causing the damper blades to close momentarily.
|
4. ORDER INFORMATION
| Manufacturer |
: |
Kyodo-Allied Industries Ltd, Singapore |
| Distributor |
: |
Kyodo-Allied Technology Pte Ltd, Singapore |
| Address |
: |
17,Kian Teck Road, Singapore 628771 |
| Contact person |
: |
Miss S N Yeh / Miss Cindy Pang |
| Tel |
: |
(65) 6265-1311 |
| Fax |
: |
(65) 6265-8100 |
| E-MAIL |
: |
sinkyodo@singnet.com.sg |
|
5. OUR PROMISES
Delivery within 7 working days or less for small quantity upon receipt of your T/T payment. We can arrange air or ocean shipment to you.
Please make your T/T payment to:
Kyodo-Allied Technology Pte Ltd
Account No: 101-908-435-9
United Overseas Bank Ltd (Main Branch)
80 Raffles Place, UOB Plaza 1 Singapore 048624
|
|
|

Our Company is committed to total quality management to ensure a constant high level of quality and services for our customer.
|
|